Analysis on Altitude Correction Factor of Corona Inception Voltage/Electric Field of AC Transmission Lines Using the Mobile Corona Cage

CHEN Yong,XIE Xiong-jie,BIAN Xing-ming,LIU Yun-peng,ZHOU Wen-jun,WANG Li-ming
DOI: https://doi.org/10.13336/j.1003-6520.hve.2010.06.015
2010-01-01
Abstract:In order to obtain the altitude correction factor of corona inception voltage of AC transmission lines in the area of 0 to 3800 meters,a mobile corona test cage was applied to research the influence of altitude changes on AC corona characteristics of several four-bundle conductors in Wuhan,Xining,Geermu,Nachitai,respectively.Photons released as a result of corona discharge on the conductors were detected by the ultraviolet detection apparatus.According to the apparent change of photon number,corona inception voltage could be acquired by the tangent method.With the obtained corona inception voltage,it was found that the existing GB/T 2317.2-2000 or GB/T 775.2-2003 was not appropriate for getting altitude correction factors.Finally,the exponential and linear correction formulas were introduced,which well fitted with the experimental values with a maximum error of 5%.