Corona Loss of HVDC Transmission Line in High Altitude Area

LI Min,ZENG Rong,YU Zhan-qing,LI Rui-hai,ZHANG Bo,LIU Lei
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.03.026
2011-01-01
Abstract:The corona phenomenon of DC transmission line in the high altitude areas would be worse than that in the low altitude areas.Measuring and evaluating the corona loss of transmission line is significant for transmission line design and economic operation.So,a kind of measurement equipment for corona loss(CL) was developed.The corona loss of UHVDC transmission line with different structure size was measured in High Voltage Technology National Engineering Laboratory(Kunming).Influences of structure size,applied voltage and conductor surface field strength were analyzed.An empirical formula for UHVDC transmission line CL prediction in high altitude area was proposed.Results show that CL increases exponentially with the applied voltage.Under the same voltage lever,total CL with bipolar voltage applied is much higher than that of mono-polar voltage applied.CL of the negative pole is slightly bigger than of positive pole.CL would be decrease with increasing of pole distance and decreasing of bundle spacing.The proposed empirical formula is more proper at high altitude(about 2100m above sea level).
What problem does this paper attempt to address?