Test Results and Analysis of Altitude-change Effect on Audible Noise of AC Corona Occurring on Conductors with Corona-test Cage

TANG Jian,HE Jin-liang,LIU Yun-peng,YANG Ying-jian,CHEN Yu-chao
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2010.04.013
2010-01-01
Abstract:High voltage power transmission faces the problem of high altitude in China. In this paper, a mobile corona test cage is firstly applied to measure the AC corona audible noises of three types of transmission bundle lines in four areas with different altitudes. The effect on audible noise from altitudes was analyzed in details. Based on linear correction relation, a correction coefficient of 3.2 dB/1 000 m was obtained which is in good agreement with the foreign coefficient 3.33 dB/1 000 m suggested by foreign colleagues. However, the test results show that AC corona audible noise of conductor does not vary with altitude in linear relation. The higher the altitude is, the smaller the altitude correction value especially in areas with altitude above 3 000 m is. Therefore, a nonlinear correction is presented based on the test data. Finally, the research results can be applicable to the case of altitude above 3 000 m and it provides insights on high altitude power engineering in China.
What problem does this paper attempt to address?