Influence Factors of Audible Noise Caused by Corona Discharge on UHVDC Transmission Lines under High Altitude Condition

TIAN Feng,YU Zhanqing,ZENG Rong,LIU Lei,LI Min,LI Ruihai
2012-01-01
Abstract:Audible noises (AN) generated by corona discharges on ultra high voltage direct current (UHVDC) transmission lines is one of the key issues of UHVDC power projects. Experimental results were obtained synchronously by 10 Briiel & Kjeer outdoor AN instruments under the full-scale test lines in National Laboratory for UHV Technology in Kunming at an altitude of 2 100 m. Long-term statistical measurements of the AN level were performed almost 24 hours a day and 5 ~ 6 days a week in 2 years. Influences of voltage, line configurations, temperature and humidity on the characteristics of AN levels were analysed. The measurement results show that the AN level rises with increasing line voltage, decreasing minimum conductor height and increasing bundle radius. The pole spacing has no significant influence on the peak value of the AN level. The AN level varies about _+ 1 dB in the temperature range of 15~22℃, and no more than ±2 dB within 6.8~24.4 ℃. The results also indicate that in a relative low range of absolute humidity, about 5 ~ 7. 99 g/ma, the AN level fluctuates slightly at different measurement points. However, in a relative high absolute humidity range, about 8 ~ 11. 5 g/ma, the AN level decreases with the increase of absolute humidity.
What problem does this paper attempt to address?