Analysis on Onset Voltage of Positive Corona on Stranded Conductors in High-altitude condition

Zhicheng Guan,Fenglin Chen,Xingming Bian,XueSong Zhao,Wenjun Yao,Liming Wang
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.04.025
2011-01-01
Abstract:The corona discharge effect is one of important problems in the design and operation of transmission lines.Energy loss,radio interference,and audible noise interference caused by corona discharge should be considered.Consequently,the impacts of air pressure and humidity on onset voltage of positive corona of transmission line were studied.Transmission lines are almost stranded conductors,thus,to calculate the onset voltage of positive corona on stranded conductors,the electric field in the vicinity of stranded conductors should be accurately calculated.The charge simulation method concerned with stranded conductors was introduced to calculate the electric field intensity.The electric field intensity of stranded conductor was 1.4 times higher than that of smooth conductor.Then the number of photoelectron on the surface of the stranded conductor was adopted to compute the onset voltage of positive corona.It is shown that calculated results of the electric field in the vicinity of stranded conductors and the onset voltage of positive corona are accurate,and corona inception voltage decreases as air pressure is lowered or humidity is raised,due to the expansion of the ionization zone and strengthening of collision ionization intensity respectively resulting from the increase of the effective ionization coefficient.