Onset Criterion for Positive Corona in Air

ZHENG Yue-sheng,HE Jin-liang,ZHANG Bo
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.03.027
2011-01-01
Abstract:It is a key step for the design of the high voltage transmission line to control the corona loss and the corona effects under a reasonable level.The evaluation of the corona onset is especially important for the corona control.We present the derivation and the simplification of a widely used criterion for coaxial cylinders considering the photoemission,and clarify the physical significance of every parameter in the criterion.Moreover,a geometric factor and its expanded expressions characterizing the photo absorption in the ionization region of the cylindrical electrode are proposed.The results by the criterion and its simplified form under different conductor radii are compared and the difference between them is significantly small under the same conditions.The results by the criterion also well agree with Peek's experimental data for a wide range of conductor radii.