Analysis on Negative DC Corona Inception Voltage of Stranded Conductors

Xiaobo Meng,Xingming Bian,Fenglin Chen,Liming Wang,Zhicheng Guan,Yingjian Yang
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.01.016
2011-01-01
Abstract:A charge simulation method was introduced to calculate the electric field intensity of stranded conductors,and a computation model was adopted to evaluate the corona inception voltage on conductors,which was established according to the gas discharge theory.The electric field intensity of stranded conductor,which is higher than that of smooth conductor,is closer to the actual situation.Then a criterion of corona inception voltage,which determined whether the primary avalanche could produce a free electron to cause the secondary avalanches,was used to calculate the corona inception voltage of conductors.The influence of air pressure on the corona inception voltage of conductors was analyzed systematically.Corona inception voltage decreased as air pressure was lowered mainly due to the enlargement of ionization zone as a result of the increase of effective ionization coefficient.Moreover,the structural parameters of transmission lines,including conductor radius,height of conductor from ground,number of bundle conductor,and bundle spacing,were studied by the computation model.
What problem does this paper attempt to address?