Equivalent Instantaneous Impedance Based Bus-Bar Protection

Xingming Deng
2010-01-01
Abstract:Following the parameter identification principle,a novel equivalent instantaneous impedance based bus-bar protection is proposed.An inductance model is developed when the internal fault occurs on the bus.Identifying the parameters of the model and analyzing the defined characteristic of the equivalent instantaneous impedance,two practical bus-bar protection criterions are put forward for distinguishing the internal fault from the external fault correctly.Compared with the traditional bus-bar protections,the current transformer saturation detection unit gets unnecessary for bus-bar protection,and the thresholds of the criterions are easy to set with high sensitivity.The new principle is suitable for non-periodic component,fundamental component and harmonic component.EMTP simulation shows the high sensitivity and reliability.
What problem does this paper attempt to address?