Analysis on eccentric bus-bar testing method of heavy current transformer

Jin Xing,Wei Zhao,Songling Huang,Bo Jiang
DOI: https://doi.org/10.1109/I2MTC.2012.6229436
2012-01-01
Abstract:For testing the reliability of heavy current transformer (HCTs) with shielding coils affected by the adjacent bus bars, an equivalent testing method called eccentric bus-bar testing method was presented in [1]. The crucial parameters of this method were also determined by analytical formulas and further verified by finite element method (FEM) in [1]. This paper presents several experiments and analytical formulas on this testing method, which reveal a basic flaw of this method. Furthermore, the practical applicability of this equivalent testing method is analyzed.
What problem does this paper attempt to address?