Experimental investigation and analytically modeling of hysteretic behavior of rigid bus-flexible connectors of 220 kV electrical substations
Tingxuan Tang,Jun He
DOI: https://doi.org/10.1007/s11803-023-2187-7
IF: 2.8
2023-05-18
Earthquake Engineering and Engineering Vibration
Abstract:This paper describes the quasi-static testing and analytical modelling of the hysteretic behavior of aluminum alloy rigid bus-flexible connectors of 220 kV electrical substations. The main objective of the study is to experimentally investigate the hysteretic behavior of six different types of rigid bus-flexible connectors 220 kV electrical substations when subjected to cyclic loading. Another objective is to theoretically study the flexibility and effectiveness of a previously proposed analytical model in fitting the experimental hysteresis loops of the tested rigid bus-flexible connectors. The experimental investigation indicates that the tested rigid bus-flexible connectors exhibit highly asymmetric hysteresis behavior along with tension stiffening effect. The theoretical study demonstrates that the generalized Bouc-Wen model has high flexibility and is effective in fitting the experimental hysteresis resisting force-displacement curves of the six tested rigid bus-flexible connectors.
engineering, civil, geological
What problem does this paper attempt to address?