Performance Comparison of Different Types of Internal Magnetic Shielding on Heavy Current Transformer

Kai-feng QU,Wei ZHAO,Bo JIANG,Peng YANG,Song-ling HUANG
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.09.008
2009-01-01
Abstract:There are two types of shielding coils which are mainly used in application, "two pairs of coils connected in opposed-polarity" and "four coils connected in parallel". To compare their performances, we mainly focused on measurement error and temperature rise. The comparison was implemented by both electric circuit analysis and physical experiments. Firstly, the currents in the shielding coils and power loss of the two methods were calculated and compared by electric circuit analysis. Secondly, measurement errors were compared by qualitative analysis. Finally, the results from theoretical analysis were verified by physical experiments. For "two pairs of coils connected in opposed-polarity" and "four coils connected in parallel", it is showed that the temperature rise of the former is not more than the later while the measurement error of the former is not less than the later. This conclusion can help design shielding coils of heavy current transformers, especially that used on the bus-bars of power stations with large capacity.