The Improved Magnetic Shield Type High T/sub C/ Superconducting Fault Current Limiter and the Transient Characteristic Simulation

GQ Zhang,ZJ Wang,M Qiu
DOI: https://doi.org/10.1109/tasc.2003.812997
IF: 1.9489
2003-01-01
IEEE Transactions on Applied Superconductivity
Abstract:Based on the equivalent circuit of a power transformer, considering both the nonlinear magnetizing characteristic of an iron-core and the nonlinear resistance of a superconducting secondary winding (V-I characteristic), the simulation of a magnetic shield type high T-c superconducting FCL was carried out by Simulink module of Matlab software. The transient response, especially the primary short circuit current is obtained. The influence of the saturation of an iron-core, and the specified structure of the magnetic circuit are analyzed. Based on the simulation, an improved magnetic shield type HTS FCL, a cross section adjustable power transformer with a multi-turn superconducting secondary winding is proposed. Its advantages include stable apparent impedance during the occurrence of a fault, shorter recovery time and lower voluminal energy dissipation during controlled S-N transition.
What problem does this paper attempt to address?