Application of Under-Impedance Criterion to Protect against Effects of Phase-to-Phase Short Circuits in Medium-Voltage Networks

Beata Zięba,Bartosz Olejnik,Iwona Grobelna
DOI: https://doi.org/10.3390/en17020505
IF: 3.2
2024-01-21
Energies
Abstract:Common overcurrent criteria used to detect phase-to-phase short circuits in medium-voltage (MV) networks in some cases do not bring the expected results. In particular, this applies to instantaneous overcurrent protections in lines with variable ranges and lines leading to local power plants (LPP), which generate a short-circuit current slightly greater than the rated current. When using overcurrent protections, there are some problems with ensuring the appropriate sensitivity and selectivity. This article proposes a protection based on impedance measurement against the effects of phase-to-phase short circuits in MV lines. The protection can be used at switchgears and also at protection points (PP) located deep in the network. The under-impedance criterion has a range independent of the value of the short-circuit current, and it can be alternative or complement to classic overcurrent protection. The introduction of these criteria allows the protection range to be independent of the type of short circuit and the short-circuit power on the busbar, and to determine this range more precisely. The under-impedance protection is particularly useful in conditions of a growing number of energy sources deep inside the networks and its automation. The main idea was to develop a uncomplicated characteristic that would ensure the possibility of setting the under-impedance protection by people who are not specialists in the field of distance protections. The characteristics have been optimally developed both in terms of the area of detected impedances and easy implementation, operation, and configuration.
energy & fuels
What problem does this paper attempt to address?
The paper mainly discusses the issue of applying the under-impedance criterion in medium voltage (MV) networks to protect lines from inter-phase short circuits. ### Main Problems the Paper Attempts to Address: 1. **Issues with Existing Overcurrent Protection**: Traditional overcurrent protection (especially instantaneous overcurrent protection) faces several challenges in medium voltage networks, such as ensuring appropriate sensitivity and selectivity, and the protection range depending on the type and value of the short-circuit current. 2. **Need for Improved Protection Schemes**: With the development of distributed generation and network automation, the structure of medium voltage networks has changed, necessitating updated protection rules to adapt to these changes. 3. **Proposal of Under-Impedance Protection**: The paper proposes a new protection scheme based on the under-impedance criterion, aiming to serve as an alternative or supplementary scheme to traditional overcurrent protection. This protection scheme is characterized by its protection range not depending on the value of the short-circuit current, and it can operate independently of the type of short circuit and the short-circuit power on the busbar. ### Specific Objectives: - Develop a simple and easy-to-set under-impedance protection characteristic, so that even non-professionals can easily configure it. - Improve the selectivity and sensitivity of protection, especially with the increasing integration of distributed generation. - Reduce the impact of voltage sags, particularly in lines using synchronous machines, adjustable electric drives, or sensitive IT equipment. - Improve operating conditions and allow for shorter protection action times, thereby reducing the impact of short circuits on system stability. Through these measures, the paper aims to provide a more reliable and easy-to-implement protection scheme for medium voltage networks to address the challenges faced by modern power grids.