Estimation Method of Short-Circuit Current Contribution of Inverter-Based Resources for Symmetrical Faults

Murillo Cobe Vargas,Oureste Elias Batista,Yongheng Yang
DOI: https://doi.org/10.3390/en16073130
IF: 3.2
2023-01-01
Energies
Abstract:This paper proposes a practical approach to estimate the symmetrical short-circuit current (SCC) levels in overcurrent protection devices (OCPDs) installed on radial feeders for any penetration level of inverter-based distributed energy resources (DERs). The proposed method restores the lost phase protection coordination by estimating SCC values and changing the TMS of OCPDs accordingly. The method is validated by comparing the results with simulations on the IEEE 34-Node Test Feeder using MATLAB/Simulink, which shows an average error of 1.5% and a maximum error of 3.0%. For a 100% penetration level, the SCC variation through OCPDs installed on the main fault trunk (MFT) exceeds ± 10%, leading to compromised phase protection coordination. The SCC flowing reversely through OCPDs on lateral branches and the fault on the MFT could cause improper tripping. Higher SCC levels are estimated and measured for fault impedances equal to zero. The phase protection is restored by changing the TMS of OCPDs using the estimated values. The study proposes two phase protection schemes to accommodate inverter-based DERs injecting 1.2 pu and 2.0 pu of SCC for a 100% penetration level. This study contributes to improving the protection coordination of distribution networks with high penetration levels of DERs. The findings have practical implications for distribution system operators and planners to maintain safe and reliable operation of distribution feeders.
What problem does this paper attempt to address?