A d-axis based current differential protection scheme for an active distribution network

Lindong Zang,Guibin Zou,Chenghan Zhou,Maoran Zheng,Tao Du
DOI: https://doi.org/10.1186/s41601-022-00243-0
IF: 10.5
2022-06-13
Protection and Control of Modern Power Systems
Abstract:Abstract The emergence of distributed generators has changed the operational mode and fault characteristics of the distribution network, in a way which can severely influence protection. This paper proposes a d-axis-based current differential protection scheme. The d-axis current characteristics of inverter-interfaced distributed generators and synchronous generators are analyzed. The differential protection criterion using sampling values of the d-axis current component is then constructed. Compared to conventional phase-based current differential protection, the proposed protection reduces the number of required communication channels, and is suitable for distribution networks with inverter-interfaced distributed generators with complex fault characteristics. Finally, a 10 kV active distribution network model is built in the PSCAD platform and protection prototypes are developed in RTDS. Superior sensitivity and fast speed are verified by simulation and RTDS-based tests.
energy & fuels,engineering, electrical & electronic