Application of Characteristic Components of Transient Signal in Grounded Wire Detection of Ineffectively Earthed Distribution Systems

Yuling Jiao
2008-01-01
Abstract:The transient signal and its transient characteristic of ineffectively earthed distribution system are researched while single-phase earth fault occurs in it.According to the fault modulus model of distributed parameters of transmission line,the distribution law of electric quantities of zero-sequence network is analyzed.Based on the characteristic component of transient signal,four fault line detection methods are presented in this paper and the single-phase earth faults under different operating conditions are simulated;the performances of different fault line detection methods are compared.Simulation results show that the presented fault line detection methods are valid and they are slightly impacted by the Perterson coil.
What problem does this paper attempt to address?