Smoke Movement and Control of Concourse Fires in Elevated Metro Station

FU Tai-ran
2007-01-01
Abstract:The most dangerous fire case in the elevated metro station is the concourse fire,which generates a large mount of smoky and toxic gases filling to hurt the passengers.The paper,taking the Guangzhou metro line 4 as the example,investigates the natural smoke exhaust design for the elevated metro station.CFD modeling is also performed to validate the design.It is indicated that the smoke control in elevation station should keep the staircase and escalator a smokeless zone,to meet this objective,two technical measures are needed:(1)the smoke screen is installed around the opening of staircase and escalator,to prevent the smoke spreading to the evacuation way,(2)the natural vent is set up on the top of the sidewall to exhaust the hot smoke in time.Furthermore the calculation method for the size and area of the natural vent is proposed.The conclusions may benefit to smoke control design and safety management for such elevation station.