Analysis and optimization of ventilation mode of exhaust smoke system in subway station fires

Ru Zhou,Jiapeng He,Juncheng Jiang
2008-01-01
Abstract:In subway station fires, the biggest immediate threat to passengers' lives is not direct exposure to fire but smoke inhalation because it contains both hot air and toxic gases. Theoretical analysis and CFD simulations were applied to analyze ventilation models with different structures, including island-platform and side-platform, in subway station fires. The results indicate that the effect of exhausting smoke of different ventilation models with different structures is quite different. The comparison of the results shows that the platform edge door plays a remarkable role in restricting the diffusion of smoke. More than 6 minutes could be ensured against the damage of smoke by using the platform edge door. The efficiency of exhausting smoke increased by not less than 10%, people could evacuate safely and effectively in time. An innovative smoke control scheme by using platform edge doors is proposed.
What problem does this paper attempt to address?