Smoke control design of deep buried metro station

Zhong Mao-hua
2006-01-01
Abstract:Deep embedment technology for metro construction reduces the influences on the transportation and high - rise building, cuts down the amount of housebreaking, and improves the condition of section construction, but also brings the challenge to the ventilation and smoke control design. Aiming to the Guangzhou metro line 6 as an example, this paper reports the smoke control design of multi - level deep buried metro station (DBMS). CFD modeling of the platform fire and train fire is performed to validate the efficiency of DBMS' ventilation and smoke control design. It is found the scheme of ventilation can produce a downward velocity of 1.5 m/s at the opening of escalator to efficiently prevent the smoke from entering the upper floor, assure the concourse level as a no - smoke zone and safety level. The evacuation stair shaft is kept positive - pressurized and smokeless. The scheme of ventilation system is able to sufficiently offer a 6 minute available time for occupant evacuation. The conclusions may benefit to the ventilation design and safety management for such deep buried station.