Full-scale MHST on Disaster Prevention System of a Metro Station (1)——Four-Marshaling Underground Two-Level Island Station

Cong-ling SHI,Mao-hua ZHONG,Xuan XU,Jie-hong SHI,Jian-yue TAO
DOI: https://doi.org/10.11731/j.issn.1673-193x.2014.09.008
2014-01-01
Abstract:Using the method of full-scale hot smoke test,a fire test is performed on the safety of disaster prevention system in a metro station,which is a type of underground two-level island,four marshaling and safety door system.By the tests,the interconnection of the disaster prevention system, accidents mode switching condition and overall safety performance is examined.The data of smoke diffusion characteristics under high security doors system,the downward velocity in the escalator opening,the available safe evacuation time are obtained by experiments.The characteristic of the asymmetric smoke flow under asymmetric exhaust volume amount design is analyzed.The results of this article can be for reference of the disaster prevention system design for domestic metro line with fourmarshaling station of 80 m long and closed system.