Full-scale experimental study on fire in one-platform-interchange elevated metro station-(3) platform fire

Maohua ZHONG,Yan XIAO,Jiapeng HU,Lei ZHANG,Bingzhou XU,Xiaokun HAO
DOI: https://doi.org/10.11731/j.issn.1673-193x.2018.06.002
2018-01-01
Abstract:To study the fire in the one-platform-interchange elevated metro station,the field fire experiments with the fire size of 0.25-1MW were carried out at the large space platform area in a one-platform-interchange elevated metro sta-tion.The smoke temperature,smoke layer height and smoke spreading time were analyzed,and the empirical models of smoke distribution at the ceiling and smoke spreading time at the platform area of this type station were established.The re-sults showed that the smoke temperature at different heights under the ceiling of the platform presented the trend of exponen-tial distribution,and the decay rate of temperature decreased with the increase of heat release rate of fire source.Under the influence of fire source location,ceiling structure and natural smoke exhaust,the smoke layer heights at different positions of the platform were different.The smoke layer height near the fire source on the platform with fire was higher,and presented the trend of gradual decrease on the longitudinal direction,while the smoke layer height at the sectional position of fire source on the platform without fire was lower,and presented the trend of gradual increase on the longitudinal direction.The hazard of the platform without fire should be paid full attention in the field emergency rescue and passenger evacuation,and the total area of smoke exhaust vents at the top of the platform in the smoke control design should be increased as large as possible to reduce the mass flow of smoke in the spreading process.The smoke spreading time was significantly affected by the heat re-lease rate of fire source,and it presented the trend of linear increase with the spreading distance on the longitudinal direc-tion.The smoke spreading velocity increased gradually with the increase of heat release rate of fire source,and the smoke spreading velocity was 0.33-0.4 m/s,0.41-0.43m/s and 0.45-0.81m/s respectively with the fire size of 0.25 MW,0.5 MW and 1MW.
What problem does this paper attempt to address?