Hot Smoke Test for Verification of the Effectiveness of Smoke Control System in a Subway Station with shielding Doors

ZHONG Wei,JI Jie,YANG Jian-peng
DOI: https://doi.org/10.3969/j.issn.1001-8360.2010.06.015
2010-01-01
Abstract:Full-scale burning tests were carried out in the Exhibition Center and the Gangxia Station of the in Shenzhen Subway to verify the effectiveness of the smoke control system.0.7 MW methanol pool fires were used in these tests;smoke temperature distribution and key-point wind velocities in the platform areas were measured.The results show as follows: Smoke on both sides of the platform descends to ground gradually during smoke extraction and induces "blind areas",the effect of smoke extraction can be improved by adding blowing vents on both sides of the platform;the effect of pressurized air supply to subway halls is closely related with the structure of the platform,i.e.,smoke can be prevented from spreading to the upper areas for those platforms without atria and the height of the smoke bay must be reduced to confine smoke in the burning area for those platforms with atria.
What problem does this paper attempt to address?