Experiment on the Smoke Blockage by Air Curtains Installed at the Front Opening of Stairs in Subway Station

Zhen-kun WU,He-ping ZHANG,Ye-hua SHENG,Zhen CHEN,Tao WENG,Long-hua HU,Xiao-chun ZHANG
DOI: https://doi.org/10.3969/j.issn.1009-0029.2013.03.007
2013-01-01
Fire Science and Technology
Abstract:Full-scale experiment of smoke blockage of air curtains were carried out in a real subway station.The smoke blockage effect of air curtain exit jet velocities and angles on scenarios of different fire source distances were studied.It was found that moderate and straight downward exit jet velocity can prevent the smoke movement very well when the fire source relative far from stairs;the smoke blockage ability of air curtain can be effectively improved by increasing the air curtain exit jet angle properly when the fire source is close to stairs;when the velocity is 5~7 m / s,and the angle is 15°~30°,the effect is the best;the smoke exhausting system is better than the air curtain,but the air curtain won ’ t influence the smoke exhausting system.
What problem does this paper attempt to address?