Numerical simulation study on ventilation mode in case of corridor fire in T-shape transfer metro station

Maohua ZHONG,Lei ZHANG,Yan XIAO,Qi MEI
DOI: https://doi.org/10.11731/j.issn.1673-193x.2017.09.002
2017-01-01
Abstract:To investigate the smoke control effect when using the co-work mode of ventilation system in different smoke con-trol zones in the hall of T-shape transfer metro station in case of corridor fire, the scenarios of passengers'luggage fire in the transfer corridor were built by using the fire dynamics software FDS, and the smoke temperature beneath ceiling, CO concen-tration and invisibility at the eye level and dangerous height under different co-work modes of ventilation system and fire-proof door in the fire corridor and the station hall on both sides were simulated.The results showed that closing the fire-proof door of the fire corridor could control the smoke in local area, but would fasten the increasing speed of CO concentration and de-creasing speed of invisibility in the corridor.When the ventilation system of each smoke control zone executed the smoke ex-haust action, the smoke would spread to the station hall on both sides, but the visibility at the dangerous height was always higher than the lowest limit value that permits safe escape.When the smoke diffused to the air supplement smoke control zone, the mixing of fresh air and smoke would fasten the descending speed of smoke, which is bad for the personnel evacua-tion and emergency rescue.