Study on External Insulation Characteristics Across Open Contacts of ±800 kV DC High Speed Switch

ZHANG Changhong,LYU Jinzhuang,LI Yixuan,LI Weiguo,ZHANG Boya,LI Mingyang,LI Xingwen,YANG Xu
DOI: https://doi.org/10.13296/j.1001⁃1609.hva.2023.05.002
2023-01-01
Abstract:HVDC high speed switch is the key equipment of multi-terminal flexible DC transmission system,it’s operation reliability is of great significance.Moreover,the insulation characteristics of the sheds play a key role in the operation stability of HSS. In this paper,the finite element model of HSS was established and the electric field distribution of HSS based on actual operating conditions was simulated.Thus,the electric field distribution of shed under rain and dirty conditions was calculated based on the obtained worst operating conditions.Additionally,the reliability of lengthening the break to improve the external insulation strength was analyzed. The results show that the worst operating condition of HSS is that one break is applied to high voltage while the other is ground.Under the rain condition,the electric field distribution of the sheds is uniform,but the electric field strength increases as a whole.Under the dirty condition,the electric field of external insulation is similar to that under the dry condition,but the electric field distortion degree at the high voltage side increases significantly.With the increase of creepage discharge distance,the electric field of external insulation decrease. The change of the break length shows less influence on the external insulation of disconnecting switch.The obtained results may provide the reference for the external insulation optimization of HSS.
What problem does this paper attempt to address?