Computation of Transient Electromagnetic Field Emission from Enclosure During GIS Disconnector Switching Operations

Zheyuan GAN,Jun ZHAO,Jiangong ZHANG,Pengkang XIE,Henglin CHEN
DOI: https://doi.org/10.13336/j.1003-6520.hve.20160310009
2016-01-01
Abstract:With the fast development of power system, intelligent equipment is increasingly applied in substations.Disconnector operation in gas insulated switchgear (GIS) always produces electromagnetic field emissions.Therefore, it has very important reference significance to analyze the electromagnetic field distribution for the electromagnetic compatibility design of the electronic equipment installed around the GIS enclosures.We established the circuit models of grounding enclosure and electromagnetic emission, and calculated the electromagnetic field caused by the enclosure current during switching operation.The results show that the electromagnetic field waveform follows the enclosure current waveform.Near the enclosure, the electromagnetic field decays fast, far from the enclosure, electric field decays linearly while magnetic field decays exponentially.With the number increasing of grounding points, the amplitude of TEV decreases obviously, and the electromagnetic field are smaller far from the bushing.The electromagnetic field near grounding enclosure is measured, and the measured results basically coincide with the calculation results.