Measurement and Analysis of Electrical Field Around Secondary Equipment of Electronic Transformer in Equivalent GIS Due to Switch Operation

Yuhao Chen,Yanzhao Xie,Kang Hui,Lin Cheng,Hui Xiang,Zhiyuan Wang,Jie Guo,Jiangping Lu
DOI: https://doi.org/10.1109/icpet55165.2022.9918438
2022-01-01
Abstract:The radiated E-field around secondary equipment of electronic current transformer and electronic voltage transformer are measured using the developed 3-D E-field measurement system under switch on operation of an equivalent 330 kV GIS system. Based on the electrically small antenna and fiber-optic transmission technology, the designed measurement system has a wide response frequency band from 10 kHz to 400 MHz. The time-domain and frequency-domain of measured signals are analyzed respectively. Under the switch on operation with charge voltage 200 kV and load 200 pF load, the maximum E-field can reach 18.67 kV/m and the frequency domain component are mainly over megahertz.