Measurement of Very Fast Transient Current Generated in Gas-insulated Switchgear

cai yuanji,tong yue,liu bin,liu xiang,liu weidong,guan yonggang
DOI: https://doi.org/10.13296/j.1001-1609.hva.2016.09.006
2016-01-01
Abstract:The very fast transient current(VFTC) induced in gas-insulated switchgear(GIS) due to operation of its disconnector may cause severe electromagnetic interference to secondary equipment. Existing related literatures focus on modelling and simulation of VFTC, or experiments in laboratory. However, no reports about on-site measurement of VFTC have been found. This study developed an on-site VFTC measurement system with a Rogowski coil as its current sensor, and the issues of filed installation and electromagnetic shielding were solved. Then, the measurement system was calibrated with test circuit in laboratory to verify its accuracy and effectiveness. The calibrated system was employed to measure the VFTC generated during operation of the disconnector in a 252 kV single phase GIS section, and the parameters of the VFTC waveforms were obtained, such as the maximum peak magnitude of 1.75 k A and the main frequencies of400 k Hz and 6 ~8 MHz. Measurement results validate the effectiveness of the developed on-site VFTC measurement system. This study may be helpful for theoretical analysis and simulation of VFTC, and may lay the foundation for studies on VFTC induced electromagnetic interference to secondary equipment in gas-insulated substations.
What problem does this paper attempt to address?