Calibration of Very Fast Transient Overvoltage Measurement System for Ultra High Voltage Gas Insulated Switchgear

岳功昌,刘卫东,陈维江,关永刚,李志兵
2012-01-01
Abstract:Very fast transient overvoltage(VFTO) is also generated during the operation of disconnect switch of gas insulated switchgear(GIS).The full waveform of VFTO includes not only high frequency components up to several tens of MHz,but also low frequency components.Therefore,the measurement system must have perfect performance of transient and steady-state response.It is very important to calibrate the frequency characteristic and voltage ratio of the measurement system in order to make sure whether the measurement system can measure the full waveform of VFTO accurately.According to the principle of wave propagation along uniform transmission line,we established an apparatus generating step voltage wave;according to the output and input signals of the measurement system,we obtained a relation between the rise time of output signal and 3 dB high cutoff frequency of the measurement system when the input signal was ideal step signal,and calibrated the high frequency characteristic using the apparatus;according to the relation between low voltage arm time constant and 3 dB low cutoff frequency,we calibrated the low frequency characteristic.The 3 dB bandwidth of the measurement system was 0.003 Hz~87.5 MHz.When the measurement system was installed in actual GIS,the voltage ratio of the measurement system was determined for power frequency voltage and lightning voltage to be 6.6×105.It is revealed that the measurement system can be used to measure full waveform of VFTO generated in ultra high voltage GIS.