Limiting the Steepness of VFTO Invaded Wave to the EHV Power Transformers Using Overhead Lines

ZHOU Hao,LI Yang,SHEN Yang,WAN Yiru,CHEN Guang,SUN Ke
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.04.026
2013-01-01
Abstract:In 500 kV substations or power plants adopting gas insulated switchgears(GIS),very fast transient overvoltage(VFTO) with a steep wavefront poses a big threat to the longitudinal insulation of power transformers.Through experiment and simulation,the effect of the overhead line between GIS bushing and transformer on the wavefront steepness of VFTO at the transformer's port was discussed.Moreover,using the software ATP-EMTP,the quantitative relation between the overhead line's length and the steepness of the VFTO at the transformer's port was also analyzed.The result shows that an overhead line with a length of 5~15 m could effectively protect the longitudinal insulation of transformers: when the length is about 5 m,the steepness of VFTO drops dramatically at the transformer's port;the steepness wouldn't exceed the restriction level for most of 500 kV substations and power plants adopting GIS when the line length is about 10 m,and for almost all variety of 500 kV substations and power plants adopting GIS,when the length reaches 15 m.