Measurement Methods of Very Fast Transient Overvoltage in Gas Insulated Switchgear with Complete Process

岳功昌,刘卫东,陈维江,关永刚,李志兵,王浩
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2011.31.007
2011-01-01
Abstract:In the design and operation of ultra high voltage(UHV) and extra high voltage(EHV) gas insulated switchgear(GIS),there is a big concern on the very fast transient overvoltages(VFTO).Experimental investigations are necessary for the full understanding of the VFTO in UHV and EHV GIS.Research was performed in this paper on VFTO measurement method.VFTO includes not only the very fast transient components,but also power frequency component and quasi-DC component(residual voltage in the floating busbar).Also,the VFTO in different GIS positions have significant different waveforms depending on the propagation and superimposition of travelling waves in GIS.Therefore,the whole process measurement of VFTO,including two aspects of the full time processes and the site distributions in GIS,is required.Based on the port-hole capacitive sensor and an impedance converting circuit,wide frequency band measurement of VFTO was realized;the measurement systems with frequency band of 0.003 Hz~100 MHz and recording time of 200 ms were developed.Synchronous measurement of VFTO in different sites of GIS was performed using several such measurement systems simultaneously;and the synchronous trigging was realized by using the electromagnetic radiation signal generated during the switching operation of the GIS disconnector.