Very Fast Transient Over-Voltages and Their Effects on Power Transformers

CHEN Shuiming,XU Jing,HE Jinliang,YANG Jianjun
DOI: https://doi.org/10.3321/j.issn:1000-0054.2005.04.038
2005-01-01
Abstract:Disconnect switch restriking causes very fast transient over-voltages (VFTO) in gas insulated substations (GIS) which can damage power equipment, especially inductance devices in the substations. The VFTO characteristics, origins, and influencing factors were analyzed to quantify the threat and evaluate mitigation methods. A typical 500 kV GIS engineering example was also analyzed. Experimental results in the literature were used to evaluate the effect of VFTO on power transformers. In the example tested in this project, the long power cable connecting the GIS to the power transformer caused the VFTO to have negligible effect on the power transformer.
What problem does this paper attempt to address?