Very fast transient overvoltage at Jiangsu Pumped-Storage Power Station

Chen Shui-ming
2006-01-01
Abstract:With the help of PSCAD/EMTDC software,the very fast transient overvoltage(VFTO) which occurs during operation on main transformers and outgoing lines in the 500 kV GIS substation for Jiangsu Pumped-Storage Power Station is calculated and analyzed,and a typical 500 kV main transformer is taken as an example to describe the effects of VFTO on main transformers during various operation.The results show that since the cables connecting the main transformer and the GIS are long(at least 200 m),the amplitude and gradient of the VFTO which transmits to every main transformer is not high,and effects of the VFTO on transformers are negligible.