Measured Impedance Based Shunt Reactor Protection Against Small Inter-turn Fault

毕大强,王祥珩,王维俭
DOI: https://doi.org/10.3321/j.issn:1000-1026.2005.03.012
2005-01-01
Abstract:By analyzing the equivalent circuit of a shunt reactor with the inter-turn fault, a kind of shunt reactor protection method against the small inter-turn fault is proposed based on the variation of the impedance measured. According to the reduced impedance measured when the inter-turn fault occurs, and using the variation of voltages as the enabling condition, this method can correctly and rapidly detect the small inter-turn fault of the shunt reactor put into operation during normal operation. The protecting method is highly reliable with the reactor on the power line, faults outside of the reactor and power system oscillating. The results of analysis show that the method can resist the saturation and open circuit of the current transformer. The settings of protection are simple and clear. The experimental results show that the protecting method is correct and practicable.