Backup Impedance Protection Sensitivity Analysis for Internal Winding Faults of Main Equipment

王维俭,桂林,唐起超
DOI: https://doi.org/10.3969/j.issn.1006-6047.2003.09.001
2003-01-01
Abstract:The impedance relay is usually used as a backup protection for large-sized generator and extra-high voltage transformer.It is misunderstood that the backup impedance protection is high-ly sensitive to the inter-phase fault,inter-turn fault and single phase-to-ground fault at star winding of the windings of generator and transformer.Actually,its sensitivity to most internal winding faults of generator and transformer is so low that it can only be used as the backup protection for the three-phase leading wires of generator and transformer,adjacent lines and bus bars.It can't be used as short-range backup protection for the generator and transformer.Digital simulation verif ies the conclusions.