Analysis of AC Faults in Converter Station and Characteristics of Its Relay Protection

成敬周,徐政
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2011.22.012
2011-01-01
Abstract:It may cause severe damages to the AC and DC systems when the faults in the AC system of converter station occur. By analyzing the characteristics of the valve commutating voltage, it can be concluded that the ground fault at the converter station will cause short circuit across the bridges and multiple complex AC faults, and the line-to-line fault will result in unbalanced commutation. The fault current is characterized as AC short circuit among multiple phases and this can be illustrated by the time function of the commutating valve current after ground fault taking place. The paper analyzes AC and DC protections by the equivalent model of the AC fault circuit. It shows that for ground faults, the valve short circuit protection and bridge differential protection can operate correctly with different current transformer (CT) locations. However, under some operating conditions, the protection system may fail to operate for line-to-line faults. In addition, sometimes the distance components of AC relay have overreach phenomenon when a AC ground fault at the high-voltage side of the valves occurs. Finally, a method using zero-sequence compensation component, which can improve the performance of the startup component, was proposed. Application to the CIGRE high voltage direct current (HVDC) benchmark model verified the analytical results.