Influence of Transverse Faults in HVAC Power System on HVDC 100hz Protection of HVDC Transmission System and Analysis on Its Characteristics

成敬周,徐政,张静
DOI: https://doi.org/10.13335/j.1000-3673.pst.2011.09.040
2011-01-01
Abstract:Faults occurred in HVAC power system will influence on backup protection of HVDC transmission system. Firstly, the analysis results based on switching function show that the main factors influencing on backup protection of HVDC transmission system are negative-sequence component in HVAC system and the third harmonic component, and the negative-sequence component is the principal factor; then the main factors influencing on backup protection of HVDC transmission system are analyzed by symmetrical component and it is found that the influences of variation of main fault parameters in HVAC system, such as fault types, position where the fault occurs, reactive power compensation and short-circuit ratio, on backup protection of HVDC transmission system are different, some are monotonic and some vary with fault types and operation modes; finally, based on the analysis result of this paper the operational range of inverse time-lag protection is determined.