The Partial Discharge Field Test of 1000kV Shunt Reactors

Jiansheng Li
DOI: https://doi.org/10.1088/1742-6596/2005/1/012169
2021-08-01
Journal of Physics: Conference Series
Abstract:Abstract Aiming at the insulation performance field diagnosis of 1000kV shunt reactors, the series resonant withstand voltage test equipment is developed. The test equipment mainly consists of the frequency conversion power supply, the excitation transformer, the series resonant capacitor, the wave blocking resistor and the voltage divider. The resonant frequency is between 30 and 300 Hz, the rated voltage is 1200kV, and the capacity is 1000 kW. During the test, the discharge is monitored at the high voltage bushing terminal and the 1000kV reactor insulation is analyzed. By using the developed test equipment, the 1000kV reactor in 1000kV Xuyi Station is tested, which verifies the validity of the on-site partial discharge measurement test.
What problem does this paper attempt to address?