Effect of Generator High-voltage-side Voltage Control on Mitigating Overvoltage in Islanded Yunnan-Guangdong UHVDC Sending System

CHEN Yiping,CHEN Lei,YE Jun,HOU Jun ],ZHANG Yao,YANG Zhongchao
DOI: https://doi.org/10.7500/AEPS20130725002
2014-01-01
Abstract:High amplitude overvoltage will occur in the AC system after the DC block in the islanded operation mode of Yunnan-Guangdong ultra-high voltage direct current UHVDC sending system.This is a key problem of islanded operation.The dynamic process of voltage can be divided into several phases.This paper analyzes the major factors influencing the overvoltage level in different phases.The overvoltage in hundreds of milliseconds after disturbance in phase two is lower than that of phase one,but the duration is longer and the criterion of voltage is higher.The voltage level of this phase is notably affected by excitation control of generators.The short-circuit ratio is closely related to the overvoltage level and the short-circuit ratio differs from phase to phase.The voltage control of the generator high-voltage-side increases the short-circuit ratio of phase two after disturbance and mitigates the overvoltage by reducing the electrical distance between the constant voltage source and the system.The rational voltage level and reactive power distribution in normal operation is guaranteed.The effectiveness of the high-voltage-side voltage control is verified by simulation results.
What problem does this paper attempt to address?