Research of Undervoltage Sensing Protection at Tuanlin Converter Station

Qingfan WU,Jinhai HUANG,Ailing ZHANG,Weidong HU,Renwei ZHOU
DOI: https://doi.org/10.13648/j.cnki.issn1674-0629.2014.04.007
2014-01-01
Abstract:According to the site feedback information of undervoltage sensing protection at Tuanlin Converter Station, this paper analy-zes the protection fault, concluding that it is caused by the failure of measurement system. Based on the structure analysis of the DC voltage signal transmission-measurement circuits and DC voltage divider, the minimum area of failure is determined. The authentica-tion with a test system identical to the control and protection equipments in the converter station is carried out, and also the RTDS, and the results show that the the protection fault is due to the DC voltage divider measurement circuit failure, and the protection acts cor-rectly. Finally, the recommendations to solve the problem is provided.