Two Fault Detection and Protection Methods for Three-Level Neutral-Point-Clamped Converters

Yuan Xibo,Li Yongdong,Wang Fred
DOI: https://doi.org/10.19595/j.cnki.1000-6753.tces.2010.06.011
2010-01-01
Abstract:This paper presents the detection and protection methods uniquely associated with three-level neutral-point-clamped voltage source converters. The line-to-ground fault can cause significant change of dc-link neutral voltage and therefore can be effectively detected and located through monitoring the voltage without extra hardware. The inner device short circuit in the three-level phase-leg can lead to dc-link voltage unbalance and doubling the stress on capacitors and devices, which must be suppressed for the safe operation of the converter. Two methods are proposed to limit the overvoltage. The design of both the ground fault detection and overvoltage limiting is covered in the paper. The schemes are verified through simulation and experiments.
What problem does this paper attempt to address?