Study on 10 kV Bus Side Overvoltage in 220 kV Leigang Substation in Foshan Power Grid

YANG Yong,ZHEN Wei-guo,WANG Yu-ming,ZHANG Fei-hua,YU Tao
DOI: https://doi.org/10.3969/j.issn.1007-290x.2010.03.009
2010-01-01
Abstract:According to the overvoltage on 10 kV bus side of transformer in 220 kV Leigang Substation in Foshan power grid,the paper analyzes the impacts of the following aspects on the voltage problem in detail: the shunt capacitor configuration of large consumers supplied directly by 10 kV system in the area,the reactive power compensation of distribution network,and cable capacitance which is greater than that of common overhead lines.The simulation model for the area is built by using computational and analytical software of power system.Case study focuses on the situation when the system operates during light load and 10 kV system is compensated by inductive reactive power.Based on the case study,an inductive reactive power compensation plan which can solve the voltage problem is achieved.
What problem does this paper attempt to address?