Effects of Random Parameters on the Lightning Flashover of Double-circuit Transmission Line

周远翔,关雪飞,吴方芳,张树林,梁前晟,高峰
2012-01-01
Abstract:Compared to single-circuit transmission line with the same voltage level,double-circuit transmission line has higher probability of lightning flashover,which is caused by structural characteristics,such as the more numbers of conductors,the higher tower-body,etc.In order to study the characteristics of double-circuit transmission line lightning flashover,according to engineering data collected from transmission lines in Xinzhou,Shanxi province,we established a simulation process applied to the double-circuit transmission line lightning flashover by the random mathematical method of Monte Carlo.The effects of random parameters in this process were discussed,and the different sensitivities to these parameters of double-circuit and single-circuit transmission line lightning flashover rate were compared.The results show that,compared to single-circuit transmission line with the same voltage level,double-circuit transmission line is more sensitive with lightning striking position,and the shielding failure flashover rate increases more quickly as the obliquity on the ground increases.After taking the power frequency voltage into consideration,the back flashover rates of double-circuit and single-circuit transmission lines are significantly increased.And with the high obliquity on the ground,the shielding failure flashover rate of single-circuit transmission line is decreased appreciably,and that of double-circuit transmission line is increased obviously.