Measurement and Analysis of the Radiated Electric Field Excited by Switching Operation of 330 kV GIS

Fei GUO,Xu KONG,Xutao WU,Jun GUO,Qing LIU,A FINIZIO,Yanzhao XIE
DOI: https://doi.org/10.13296/j.1001-1609.hva.2014.09.021
2014-01-01
Abstract:To realize on-line monitoring of GIS, the radiation field, excited by very fast transient overvoltage(VFTO)during the operation of the breakers and the disconnecting switches,was measured and analyzed. First, a measuring system for the radiation field excited by VFTO was developed, and calibration results show that this measuring system has the features of anti-interference and wide-band response. Second, the system was applied to measure the radiation field excited by VFTO in a 330 kV GIS, and the results indicate that there is a significant difference between the radiation fields due to the operations of breaker and disconnecting switch. Even for same switch, different operation causes different radiation field. Analysis reveals a close relation between the discharge position and the energy distribution of the discharge-induced frequency spectrum.
What problem does this paper attempt to address?