Effect of Breaker Structural Parameters on Very Fast-fronted Transient Overvoltage Waveform in GIS

SHAO Chong,YANG Yu,LIU Wei-dong,WANG Zan-ji
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.03.040
2011-01-01
Abstract:The double-fracture circuit-breaker with two grading capacitors is used in gas insulated substation(GIS) at 550kV and above voltage levels.This article focuses on the effect of some parameters of circuit-breaker on very fast-fronted transient overvoltage(VFTO) waveform in GIS,such as the shunt capacitance of circuit breakers,floating bus,grounding switch status and so on.First,a simplified GIS model considering the circuit breaker structure was established.The analytical solution in frequency domain of node voltage was derived out from this model.Then,the effects of these parameters were analyzed.The results showed that when the capacitances of shunt capacitors or the capacitance to ground or the length of bus between circuit-breaker and disconnector increased,the main frequency of VFTO decreased,but the amplitude of each frequency at different nods had different variations,indicating that the amplitude of VFTO at the end of the no load bus decreased,the rising edge tended to be gentle;the amplitude and the gradient of the rising edge at the entrance of transformer slightly changed,but the rising time increased.When the grounding switch was off,the voltage between the breaker fractures was low,but the voltage to ground might be higher;when the grounding switch was closed,overvoltage between the fractures and fractures to ground might occur due to resonance.Therefore these phenomena should be paid attention to in the design of circuit-breakers.