Parameter Selection of Overhead Shield Wires For±800 Kv Ultra-high Voltage DC Yard

HU Jun,LI Wei,HE Jin-liang,LIU Ze-hong,YU Jun,GAO Li-ying,YU Zheng
DOI: https://doi.org/10.13336/j.1003-6520.hve.2010.01.013
2010-01-01
Abstract:The lightning protection in the DC yard is a key problem of the ±800 kV UHVDC power transmission systems.Since the lightning rods in the DC yard can not meet the demands of lightning protection,the densely packed shield wires are proposed,showing a better effect than the lightning rods.The numerical method is applied to analyze the parameters of the shied wires.The safety clearance between the shield wire and the bus or apparatus is considered for the parameter selection of the shield wire.In addition,the surface electric field of the shield wire should also be small enough to avoid the corona discharge.As a conclusion,the duplex shield wires surpass the single shield wire due to the relatively low surface electric field and the robustness against the wire breaking.Finally,the diameter and the height of the shield wire above the bus or apparatus are provided,which had been adopted in the shield wire designs of Xiangjiaba-Shanghai and Jinping-Sunan ±800 kV UHVDC yards.
What problem does this paper attempt to address?