Simulation of Artificial Contamination Test Considering Hysteresis & Saturation Characteristic of Transformer
LIN Hui,HE Bo,HUI A-li
DOI: https://doi.org/10.3969/j.issn.1003-6520.2007.10.005
2007-01-01
Abstract:To explore the effect of testing transformer during test in detail and to analyze the difference between testing data and spot data in the whole period of flashover,the model of artificial insulator test was set up with taking into account the transformers' characteristics such as capacity,hysteresis,etc.A typical test was simulated through toolbox provided by the Matlab software.Through comparing the simulating results of typical transformer with those of the ideal transformer,it is found that,in the artificial contaminated test,the biggish copper lose leads to the distinct load effect,the soft magnetization leads to the marked excitation flow,and the nonlinear excitation characteristic leads to the distinct harmonic in leakage current.The results is beneficial to modifying the data of artificial contamination test,studying the mechanism of flashover,and developing the method of detecting and predicting flashover,etc.
What problem does this paper attempt to address?