High-current Arc Test and Characteristic Research in Converter Transformer

Jun Deng,Zhicheng Xie,Zhicheng Pan,Chen Liang
DOI: https://doi.org/10.1109/cieec54735.2022.9846232
2022-01-01
Abstract:Aiming at the problems of fuel tank rupture and explosion caused by the internal discharge during the operation of HVDC converter transformers, the test principles and methods for simulating the failure of the converter on-load tap-changer, bushing riser and body were discussed. The arc test model was designed and manufactured. The arc test with a rated current of 25kA and a fault cumulative energy value of 1.46MJ~13.89MJ was carried out. The laws of current, arc voltage and cumulative energy in the dynamic development process of arc discharge fault were revealed. The real test data and test analysis methods are provided for the anti-explosion design of the converter transformer, the function verification of the quick pressure relief device and the analysis of the cause of the arc fault.
What problem does this paper attempt to address?