An Improved Continuous Commutation Failure Mitigation Method in High Voltage Direct Current Transmission System

Guohui Zhang,Liuming Jing,Meng Liu,Bin Wang,Xinzhou Dong
DOI: https://doi.org/10.1109/CICED.2018.8592449
2018-01-01
Abstract:High-voltage direct current (HVDC) transmission systems have developed rapidly in China. Strong DC and weak AC power grids have some limitations, and cascading faults caused by HVDC commutation failures is a serious problem in high voltage AC/DC hybrid power grids. The lack of self-turn-off ability of semiconductor switch causes commutation failure. The first commutation failure is inevitable. However, the continuous commutation failure can be prevented by the proper control method. The key point is the duration time and values of advancing firing control and the extinction angle dynamic control. Hence, an improved method based on constant extinction area is proposed. The proposed method is based on the dynamic change of extinction angle in the inverter side and superimposed advancing firing control in the rectifier side. The proposed method is tested on a hybrid system with two HVDC transmission systems and one AC interconnection line. The model was developed using the electromagnetic transient software package PSCAD/EMTDC.
What problem does this paper attempt to address?