The Link and It's Back-to-Back Rated Operational Tests of 50MVA STATCOM

Wenhua LIU,Qiang Song,Dongjiang Zhang,Tianjin Chen
DOI: https://doi.org/10.3321/j.issn:1000-6753.2005.02.003
2005-01-01
Abstract:The 50MVA STATCOM installed at Shanghai Xijiao substation employs chain-circuit inverter based on IGCTs, and each phase comprises 10 single phase voltage-sourced inverters (Links) and outputs 10 kV voltage. To verify the overall design of Link including connection of IGCT's, control, protection, cooling and EMC, it's necessary to test the Links in rated operation mode. In the tests, two Links are connected back-to-back via a inductor, one is controlled to operate in leading mode and the other in lagging mode, and power losses are provided by a DC power supply connected to one of the dc capacitors. The principle and design of the Link, the principle and the results of back-to-back tests are given in this paper. Tests results confirmed that all performance requirements were met.
What problem does this paper attempt to address?